InteliLite Global Guide
201
Subgroup: Frequency Protection
Setpoint group Generator settings Related FW 1.2.1
Range [units]
Generator > Frequency Wrn (page 201) .. 200,0 [%]
Default value 110,0 % Alternative config NO
Step
0,1 % of Nominal Frequency (page 159)
Comm object 8296 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator phase L1 overfrequency.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Generator > Frequency BOC
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.2.1
Range [units]
Generator < Frequency Wrn (page 202) .. Generator > Frequency BOC (page 201) [%]
Default value 110,0 % Alternative config NO
Step
0,1 % of Nominal Frequency (page 159)
Comm object 9688 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator phase L1 overfrequency.
Generator > Frequency Wrn
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.2.1
Range [units]
0,0 .. Generator < Frequency Wrn (page 202) [%]
Default value 85,0 % Alternative config NO
Step
0,1 % of Nominal Frequency (page 159)
Comm object 8298 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator phase L1 underfrequency.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Generator < Frequency BOC
6 back to List of setpoints