InteliLite Global Guide
469
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1421
Description
The output is closed when there is the shutdown or BOC alarm from the COOLANT TEMP (PAGE 543) in the
alarmlist or isn’t confirmed.
AL CoolantTemp Sd
6 Logical binary outputs alphabetically (page 463)
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1420
Description
The output is closed when there is the warning alarm from the COOLANT TEMP (PAGE 543) in the alarmlist or
isn’t confirmed.
Note: Binary output is also active if protection type is set to HistRecOnl and threshold level for history
record is reach.
AL CoolantTemp Wrn
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1260
Description
This output is active when the Wrn Charging Alternator Fail (page 567) alarm is present in the alarmlist or
isn’t confirm.
AL D+ Fail
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1294
Description
This output is active when the Sd Earth Fault Current (page 585) alarm is present in alarm list or isn’t
confirm.
Note: It is strongly recommended to use this output only onetime.
AL Earth Fault
6 back to Logical binary outputs alphabetically

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals