InteliLite Global Guide
585
Related applications AMF, MRS
Description
This alarm evaluates the unbalance of the phase currents, i.e. the difference
between highest and lowest phase current at any given time. The following
setpoints are related to it:
Current Unbalance BOC (page 197) adjusts the maximum allowed difference
between the highest and lowest phase current at any given time.
Current Unbalance BOC Delay (page 197) adjusts the alarm delay.
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Earth Fault Current
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the value of earth fault current is higher than adjusted
limit. The following setpoints are related to it:
Earth Fault Sd (page 340) adjusts the maximum allowed earth fault current.
Earth Fault Delay (page 339) adjusts the alarm delay.
Sd Earth Fault Current
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Fence 1 Alarm
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm evaluates the GPSposition of gen-set. The following setpoint are
related to it:
Geo-Fencing (page 285)
Fence 1 Protection (page 286)
Fence Radius 1 (page 284)
Sd Fence 1 Alarm
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Fence 2 Alarm
Alarm evaluated All the time
Sd Fence 2 Alarm

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals