InteliLite Global Guide
597
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phases 3. The following
setpoints are related to it:
Generator < Voltage BOC (page 199)
Generator <> Voltage Delay (page 200)
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator L3L1 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 3 and
1. The following setpoints are related to it:
Generator < Voltage BOC (page 199)
Generator <> Voltage Delay (page 200)
BOC Generator L3L1 < Voltage
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator > Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator > Frequency BOC (page 201)
Generator <> Frequency BOC Delay (page 202)
BOC Generator > Frequency
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator < Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator < Frequency BOC (page 201)
Generator <> Frequency BOC Delay (page 202)
BOC Generator < Frequency
6 back to List of alarms level 2