User Interface
113 / 135
4. To modify “Reactive power set in per” to -20%, the following instruction can be
issued:
00 00 00 00 00 06 01 06 30 4C FF EC
5. To change the local / remote control item to remote control mode, the following
instruction can be issued:
00 00 00 00 00 06 01 06 30 9C 00 01
6. To have the PCS power-off in local control mode, the following instruction can
be issued:
00 00 00 00 00 06 01 06 30 AB 55 55
7. To have the PCS power-on in remote control mode, the following instruction can
be issued:
00 00 00 00 00 06 01 06 31 0E 00 01