Refer to table 6-12 below for information about the parameter description, setup
range, lower limit, default and upper limit of these parameters.
Table 6-12 Remote Data Parameters
Parameter name
Description
Setup range (lower limit,
default, upper limit)
IEEE1547-2018
wBatteryPortVolt
Battery port voltage
{0.0, 0.0,1600.0 V}
fBatteryReady
Battery ready signal
{Ready}
fBatteryPreChargeEn
Battery precharging
enable/disable
{Disable}
wBatteryPower
Current battery power
{-220.0, 0.0, 220.0 Kw}
wRemoteCurrFormOut
Current battery current
{-225.0, 0.00, 225.0 A}
wRemoteChargeVoltLimit
Remote battery charging
voltage limit
{875.0,950.0,1550.0 V}
wRemoteDisChargeVoltLimit
Remote battery discharge
voltage limit
{875.0,875.0,1550.0 V}
wRemoteChargeCurrLimit
Remote battery charging
current limit
{-220.0, -220.0,0.0A}
wRemoteDisChargeCurrLimit
Remote battery discharging
current limit
{0.00, 220.0, 220.0 A}
wRemoteFloatChargeVolt
Remote battery float charging
voltage setting
{875.0,950.0,1550.0 V}
wRemoteFloatChargeCurr
Remote battery float charging
current setting
{-220.0, -10.0,0.0A}