Table 6-5 HVRT Parameters (IEEE1547-2018, Rule21 and ISO-NE )
HVRT
Setting Range
Parameter
Name
Description
IEEE1547-2018
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Default
Max
HVRTVolt
(1,2) (%)
Threshold value of
high voltage ride
through (1
st
& 2
nd
point)
100
100
125
125
135
135
100
100
125
125
135
135
100
100
120
120
135
135
HVRTTime
(1,2) (s)
Time of Level high
voltage ride through
(1
st
& 2
nd
point)
0
0
0
0.16
655
655
0
0
0
0.11
655
655
0
0
0
0.16
655
655
HVRTVolt
(3,4) (%)
Threshold value of
high voltage ride
through (3
rd
& 4
th
point)
100
100
120
120
135
135
100
100
120
120
135
135
100
100
120
117.5
135
135
HVRTTime
(3,4) (s)
Time of Level high
voltage ride through
(3
rd
& 4
th
point)
0
0
0.16
12
655
655
0
0
0.11
12.50
655
655
0
0
0.25
0.25
655
655
HVRTVolt
(5,6) (%)
Threshold value of
high voltage ride
through (5
th
& 6
th
point)
100
100
110
110
135
135
0
0
110
110
135
135
100
100
117.5
115
135
135
HVRTTime
(5,6) (s)
Time of Level high
voltage ride through
(5
th
& 6
th
point)
0
0
12
12
655
655
0
0
12.5
12.5
655
655
0
0
0.55
0.55
655
655
HVRTVolt
(7,8) (%)
Threshold value of
high voltage ride
through (7
th
& 8
th
point)
100
100
110
110
135
135
100
100
110
110
135
135
100
100
115
110
135
135
HVRTTime
(7,8) (s)
Time of Level high
voltage ride through
(7
th
& 8
th
point)
0
0
12
12
655
655
0
0
12.5
12.5
655
655
0
0
1.05
1.05
655
655

Table of Contents