139
10 Technical Data
10.1 Datasheet
Model Name
SCA50KTL-
DO/US-480
SCA60KTL-
DO/US-480
SCA36KTL-DO/US-480
DC Input
Max. PV Power
90kW
(33kW per MPPT)
61.2kW
(22.44kW per MPPT)
Max. DC Input Voltage
1000VDC
Operating DC Input
Voltage Range
200-950VDC
Start-up DC Input Voltage /
Power
330V / 80W
Number of MPP Trackers
3
MPPT Voltage Range
480-850VDC
540-850VDC
400-850Vdc
Max.PV Short-Circuit
Current (Isc x 1.25)
204A (68A per MPPT)
Number of DC Inputs
15 inputs, 5 per MPPT
DC Disconnection Type
Load rated DC switch
DC Surge Protection
Type II MOV, 2800VC, 20kA ITM (8/20μS)
AC Output
Rated AC Output Power @
PF>0.99 to ±0.91
1
50kW
60kW
36kW
Max. AC Apparent Power
(Selectable)
50kVA/55kVA
60kVA/66kVA
36kVA
Rated Output Voltage
480VAC
Output Voltage Range
2
422-528VAC
Grid Connection Type
/PE/N (Neutral optional)
Max. AC Output Current
@480V
AC
60.2A/66.2A
72.2A/79.4A
43.5A
Max AC OCPD Rating
110A
125A
125A
Rated Output Frequency
60Hz
Output Frequency Range
2
57-63 Hz
Power Factor
>0.99 (±0.8 adjustable)
Current THD
<3%
Max. Fault Current
Contribution (1 Cycle RMS)
64.1A (1.06/0.88 PU)
73.2 A (1.68 PU)
AC Disconnection Type
Load rated AC switch
1)
Active Power Derating begins; at PF=±0.91 to ±0.8 when Max AC Apparent Power is set to 55 or 66kVA.
2)
The "Output Voltage Range" and "Output Frequency Range" may differ according to the specific grid standard.