11
11
/
156
High Protection Degree: Powder coated aluminum NEMA 4X enclosure
meets the demanding needs of both indoor and outdoor use.
Intelligent Integration: Integrated DC/AC disconnect switches, and up to
15 fused string inputs eliminate the need for external DC combiner boxes,
simplifying installation and the need for DC BOS equipment. The rapid
shutdown version wireboxes have integrated the rapid shutdown PLC
transmitter, requiring no field wiring, and eliminated the negative DC fuses
in accordance with the 2017/2020 National Electric Code.
2.3 Product Protection and Functions
AC output voltage and frequency monitoring
Anti-islanding detection with bi-directional frequency perturbation
DC input and AC output over-voltage protection
DC input and AC output over-current protection
DC input insulation to ground monitoring
DC injection of AC output
DC Arc-fault detection and circuit interruption
Leakage current to ground monitoring
Internal enclosure temperature monitoring
IGBT power module temperature monitoring
KVA overhead to enable full rated Active Power from unity PF to 0.91 PF
(Only for SCA50/60KTL)
Load rejection over voltage (LROV) protection
No neutral connection required - delta connection permitted with external
AC GFCI
PVRSS certified rapid shutdown compliant to 2017/2020 NEC (with
RSD version wireboxes only).