6.2.4 LVRT/HVRT Parameters
LVRT/HVRT” is used to set the LVRT and HVRT parameters. Move the
cursor to this item and press the ENT key to set the parameters. There
are 7 pages of LVRT/HVRT parameter settings. These can be changed
in the menu tree or by the LVRT (Figure 6-11) and HVRT (Figure 6-12)
graphs.
LVRTTime1(s)
LVRTVol1
P1/7
1.00
0.00%
0.00
0.00%
LVRTVol2
50.00%
1.00
P2/7
10.00
70.00%
10.00
50.00%
70.00%
20.00
LVRTTime2(s)
LVRTTime3(s)
LVRTVol3
LVRTVol4
LVRTTime4(s)
LVRTVol5
LVRTTime5(s)
LVRTTime6(s)
LVRTVol6
LVRT Curve LVRT Curve
P3/7
20.00
88.00%
20.00
88.00%
LVRTTime7(s)
LVRTTime8(s)
LVRTVol7
LVRTVol8
LVRT Curve
HVRTTime1(s)
HVRTVol1
P4/7
0.16
125.00%
0.00
125.00%
HVRTVol2
120.00%
0.16
HVRTTime2(s)
HVRTTime3(s)
HVRTVol3
HVRT Curve
P5/7
12.00
110.00%
12.00
120.00%
110.00%
12.00
HVRTVol4
HVRTTime4(s)
HVRTVol5
HVRTTime5(s)
HVRTTime6(s)
HVRTVol6
HVRT Curve
P6/7
12.00
110.00%
12.00
110.00%
HVRTTime7(s)
HVRTTime8(s)
HVRTVol7
HVRTVol8
HVRT Curve
LVRT and HVRT Control
LVRTTripVolt
LVRTModeSetting
P7/7
200.0%
200.0%
88.0%
2
LVRTPstReactiveI
1
110.0%
HVRTTripVolt
HVRTModeSetting
LVRTNegReactiveI
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
Figure 6-1 L/HRVT Parameter Settings