Control Command
Control Command
P1/2
MPPT Scan
P2/2
6.2.2 Control Command
There are five submenus in the Control Command menu:
Force Restart
Factory Defaults
ARC Detect
ARC Clear
PV1
PV2
PV3
Time
Vmppt(V)
0
0
0
Pmppt(kW)
0.0
0.0
0.0
Udc(V)
0.0
0.0
0.0
Idc(A)
0.0
0.0
0.0
Figure 6-8 Control Command Setting
1. Force Restart. If a fault shutdown happens, a severe fault may have
occurred inside the inverter. The user can perform a force reboot for
one time in this menu if the user needs to restart the inverter.
INSTRUCTION:
Force Restart is effective only when the faults “IntFault0010~0150”
in the troubleshooting table occur. The inverter may restore to normal
operation automatically if alarm or protection faults occur. This
function will not respond when the inverter is in operation mode and a
“FaultOperated” alarm interface will be indicated.
2. Factory Default. The manufacturer’s parameter default values can
be restored when the inverter is not in operation mode. Otherwise
“Fault Operated” will be reported.