107
Table 6-11 Other Parameters
Other Parameters
Setting Range
Parameter Name
Description
IEEE1547-2018
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Default
Max
PowerOnDelay (s)
Startup delay
time
1
300
1200
1
300
1200
1
300
1200
ReactivePowerStep
(%/P)
Reactive power
adjustment step
0.01
25
600
0.01
25
600
0.01
25
600
eErrSoftStarTms
(s)
Power startup
time after Grid
Fault
1
300
1000
1
50
1000
1
600
1000
eNormSoftStopTms
(s)
Normal power
time in soft stop
1
1
1000
1
10
1000
1
10
1000
eNormSoftStartTms
(s)
Normal power
time in soft
startup
1
1
1000
1
1
1000
1
50
1000
NormalDeratingStep
Power step in
Derarting
0.01
100
100
0.01
100
100
0.01
6
100
PVSlowStartStep
(%/P)
PV power
sudden change
slow start step
size
0.01
10
100
0.01
10
100
0.01
10
100
PVSlowStartPwDelt
a
PV power
sudden change
slow start power
limit increment
0.01
5
10
0.01
5
10
0.01
5
10
FaultPowerT(C)
The trigger
temperature of
module (C)
95
95
95
95
95
95
95
95
95
FaultEnvT(C)
The trigger
temperature of
enviroment (C)
83
83
83
83
83
83
83
83
83
GFCIStaticValue
(mA)
The static
threshold value
of Leakage
current
100
540
1000
100
540
1000
100
540
1000
GFCIStaticT (s)
The static
threshold time of
0
0.2
655
0
0.20
655
0
0.2
655