EasyManua.ls Logo

CPS SCA36KTL-DO/US-480 - Page 94

CPS SCA36KTL-DO/US-480
156 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
87
Table 6-1 Protection Parameters (IEEE1547-2018, Rule21 and ISO-NE)
Grid Voltage Protection
Setting Range
Parameter name
Description
(Threshold Value
of)
IEEE1547-2018
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Default
Max
GridVoltMax1(%)
Level 1 Max. grid
voltage
100
110
135
100
110
135
100
110
135
VoltMaxTripTime1(S)
Level 1 Max. grid
trip voltage
0
13
655
0
12.5
655
0
2
655
GridVoltMax2(%)
Level 2 Max. grid
voltage
100
120
135
100
120
135
100
120
135
VoltMaxTripTime2(S)
Level 2 Max. grid
trip voltage
0
0.16
655
0
0.16
655
0
0.16
655
GridVoltMax3(%)
Level 3 Max. grid
voltage
100
120
135
100
120
135
100
120
135
VoltMaxTripTime3(S)
Level 3 Max. grid
trip voltage
0
0.16
655
0
0.16
655
0
0.16
655
GridVoltMin1(%)
Level 1 Min. grid
voltage
0
88
100
0
88
100
0
88
100
VoltMinTripTime1(S)
Level 1 Min. grid
trip voltage
0
21
655
0
20.5
655
0
2
655
GridVoltMin2(%)
Level 2 Min. grid
voltage
0
50
100
0
70
100
0
50
100
VoltMinTripTime2(S)
Level 2 Min. grid
trip voltage
0
2
655
0
10.5
655
0
1.1
655
GridVoltMin3(%)
Level 3 Min. grid
voltage
0
50
100
60
50
100
0
50
100
VoltMinTripTime3(S)
Level 3 Min. grid
trip voltage
0
2
655
0
1.5
655
0
1.1
655

Table of Contents