THE REFRIGERATION UNIT IN THIS MACHINE DOES NOT CONTAIN ANY USER
SERVICEABLE PARTS.
In the event of any failure the entire unit must be returned complete to Crane Merchandising
Systems. Due to the presence of flammable refrigerant, ground shipment must be used for
transportation only.
Onsite repair of the sealed system, including evacuation of the unit, recharging, brazing, soldering or any other
heat producing method, is strictly prohibited. These tasks must only occur in a facility specifically equipped to
handle flammable refrigerants.
COMPONENTS
OMRON POWER SUPPLY 24V 150W
The New OMRON 24V 150W Power Supply is located inside the service area, mounted to the
back wall below the AC Distribution Box. It has 3 outputs with each one being capable of 150W.
Two of the outputs are wired into the AC Distribution Box. Each of the outputs are fused at
75W by the circuit breakers in the AC Distribution Box Assembly. It contains a Board with Green
Status Light that illuminates when power is present. This OMRON 24V 150W Power Supply is
common across all New Electronics Platform BevMAX Refresh Domestic, Export, Classic
(BevMAX 4), and Media (BevMAX 6) models. The OMRON Power Supply receives AC voltage via
the AC Distribution Box. The OMRON Power Supply converts the AC voltage to the main
operating DC voltages of the Vender (24VDC).
POWER AC DISTRIBUTION BOX
The AC Distribution Box is located inside the service area, mounted to the back wall above the
OMRON Power Supply. It is where the 120VAC or 220VAC input voltage is sent to the
Refrigeration Unit & Condenser Fan, Evaporator Fan, and OMRON Power Supply which
converts the AC voltage to the main operating voltages of the Vender (24VDC).
The main operating voltages are sent to the AC Distribution Box. It contains an independent
Environmental Board for improved troubleshooting and to distribute AC power to the
Compressor, Evaporator/Condenser Fans, and DC power to the Media Atlas H Board, LED
Lighting and Encapsulated Temperature Sensor. The Compressor, two vertical side LED Light
Strips, and the Encapsulated Temperature Sensor are not powered up when the Machine
turns on. The Compressor turns on 2 minutes after the Machine is powered on. The two side
LED Light Strips, Evaporator Fan, and Encapsulated Temperature Sensor turn on when the
Environmental Board begins to communicate to the Media Atlas H Board. Two 3 Amp circuit breakers protect
the 24VDC supply. One is for the Cabinet and the other is for the Door electronics. This AC Distribution Box is
common across all New BevMAX Refresh Domestic, Export, Classic (BevMAX 4), and Media (BevMAX 6) models.