MACHINE NOT COOLING
Condenser Fan or
Evaporator Fan not
running.
Evaporator is iced
up.
Clean Condenser.
Replace Encapsulated Temp. Sensor.
Machine not
cooling.
Dirty or clogged
Condenser.
Clear Rear Screen of obstructions. Ensure
rear of Cabinet is at least 4ā€ (10cm) from
wall.
Defective
Encapsulated Temp.
Sensor.
Move Machine.
Machine in direct
sunlight or near a
heat source.
Replace faulty seal(s).
Restricted airflow.
Check Fan Blades for obstruction. Check Fan circuit.
134a - Replace as necessary.
R290 – Replace the refrigeration Deck and return it to
Crane
Check for air leaks or clogged Condensate
drain.
Move Machine.
Machine in location
with humidity above
70%.
Faulty Product area
seal(s).