COMPRESSOR WILL NOT START
Defective starting
component
(capacitor, relay).
Close Service Door.
Check Harness from Compressor to AC
Distribution Box.
Compressor will
not start.
Service Door is
open.
Compressor is
unplugged.
Replace Service Door Switch.
Defective Door
Switch.
Check power source at outlet.
Replace Encapsulated Temp. Sensor.
Low voltage.
Defective
Encapsulated
Temp. Sensor.
Press Toggle Compressor, see if you can
turn the compressor on
Go to Test >
Refrigeration
System
134a -Replace starting component.
R290 – Replace the Refrigeration
Deck and return it to Crane
Defective
Compressor.
Defective
Environmental Board
in AC Distribution
Box.
134a -Replace Compressor.
R290 – Replace the Refrigeration
Deck and return it to Crane
Replace Environmental Board.