Page 44
P833E
Display software version
- This address will cause t h e
panel software version to be flashed back at the
keypad.
P849E Active Time-Zones - If Time Zones are being used, b y
entering in this address while in Installation Program M o d e
the panel will display any of the 8 time zones currently active. If LED’s 1-8 are On they indicate
active time zones.
SETTING THE REAL TIME CLOCK
P823E - P827E
These addresses are used to set the internal real time clock used by the time zone functions, time & date stamping
of events in the event buffer and the time for any automatic test calls to a monitoring station.
P823E 1-7E Set day of the week - where values of 1-7 represent Sunday to Saturday (Sunday = 1)
P824E 0000 - 2359E Set time - Use 24 hour format
P825E 1-31E
Set day of the month
- where values of 1-31
represent days in the month.
P826E 1-12E Set Month - where values of 1-12 represent t h e
month.
P827E 0-99 Set Year - Where 0-99 represent years, i.e. 02 =
2002.
TEMPORARY OUTPUT DISABLE
P837E Temporary Output Disable - This address allows a
technician to select any output/s to be temporarily
disabled for one alarm or armed cycle, e.g. by turning on
LEDS 1-8 at P837E then leaving program mode,
outputs 1-8 will not turn on following any alarms. The technician is now free to arm the system to
test all monitoring signals without having all of the internal & external alarms activating. When the
alarm is reset or disarmed all outputs will now work normally again.
EE² LOCAL UP/DOWN LOAD
P838E
Write to EE² Board
- with the optional back-up EE² board plugged into the serial connector on
the panel and the write enable link fitted on the EE² board, entering P838E will write a copy of the
panel program files to the EE² board.
P839E
Read from EE² Board - this address allows a copy of a panel program files to be downloaded
into a panel (the program files must first have been copied to the EE² board - refer P838E). Note:
When transferring data from this board to a panel, the software versions of the two panels (the
Clear all outputs
0
Reset Communicat
Event Printing
Walk Test