IM 817-4 Page 21 of 60
Typical Valve Packages
The optional factory-supplied Daikin Control Valve(s) for water
applications can be either 2-way or 3-way type, and is / are shipped
separate from the unit ventilator itself to help avoid shipping damage
to the piping of the connection stub from the weight of the valve, and
toprovidetheinstallerwithmaximumexibilityinmakingtheeld
pipingconnection. Beforeproceeding,seegures 60 through84as
applicable,aswellasthejob-specicpipingdrawings.
Notes:
1. See label furnished on 2-way valve to determine direction of ow
through the valve.
2. Adhere to the port orientation shown for the 3-way valve.
3. For hot water applications and chilled water/hot water (2-pipe)
applications, the 2-way valve furnished is normally piped open to
the coil; the 3-way valve is piped normally open to the coil.
4. For chilled water applications, the 2-way valve furnished is normally
piped closed to the coil; the 3-way valve is piped normally closed to
the coil.
5. The 3-way valve is generally selected for diverting water back to the
return main, where a constant pump head pressure is required.
6. All water coil stubs are 7/8" I.D. female sweat. Coil connections
terminate 9" (229mm) from the end of the unit. Hot water connections
may be same end as cooling coil connections, but are recommended
to be at opposite ends from each other. When using MicroTech II
controls, they must be at opposite ends.
Face and Bypass – MicroTech
II™
2-Way and 3-Way End-of-Cycle Valves
Control 2 Position
Electrical 24 VAC, 50/60 Hz
Stroke Power Stroke 9 to 11 seconds
Spring return 4 to 5 seconds
Ambient 32
o
F to 125
o
F (0
o
C to 52
o
C)
Connections
3
⁄
4
"
FNPT
Static Pressure 300 psi (2100 kPa)
Close-Off Pressure 13 psi (90 kPa)
Temperature 32
o
F to 200
o
F (0
o
C to 93
o
C)
Connections
3
⁄
4
"
FNPT, 1" FNPT
Static Pressure 300 psi (2100 kPa)
Close-Off Pressure 13 psi and 15 psi
(90 kPa and 103 kPa)
Temperature 32
o
F to 200
o
F (0
o
C to 93
o
C)
Control 2 Position
Electrical 24 VAC, 50/60 Hz
Stroke
Power Stroke 9 to 11 seconds
Spring return 4 to 5 seconds
Ambient 32
o
F to 125
o
F (0
o
C to 52
o
C)
Table 10 - 2-way Actuator
Table 11 - 2-way Valve Body
Table 12 - 3-way Actuator
Table 13 - 3-way Valve Body
Table 14 - EOC Connection
Figure 61 - 3-way End of Cycle Valve
Figure 60 - 2-way End of Cycle Valve
Connection C
v
X Y Z
3
⁄
4
"(19mm) FNPT 7.0 1
11
⁄
16
" (43mm)
11
⁄
16
" (23mm) 3
5
⁄
8
" (92mm)
*1"(25mm) FNPT 7.0 1
7
⁄
8
" (47mm) 1" (25mm) 3
11
⁄
16
" (94mm)
* 1" valve for steam only