Page 56 of 60 IM 817-4
Units must have a lter installed when operating. Operation
without a lter can compromise unit performance due to build
up of dust and dirt on components.
Filter(s)
Turn off the unit, (fan speed switch or unit on/off switch is located
behind the right front end compartment panel). Remove the center
frontpanel,pulloutthelterandreplacewithacleanlter.Replace
the center panel and restart the unit.
Filtersshouldbereplacedduringtherstweekofplacingintoservice
to prevent dirt carry-over into the internals of the unit and back into
theclassroom,(seegure136).Aperiodiclterchangeoutprogram
should be established. Filters should be checked monthly or more often
if conditions indicate. Filters are included in all units. Daikin single-
useltersarestandardonallbutelectricheatunits,whichcomewith
permanentwiremeshlters.Permanentwiremeshandrenewablemedia
ltersareavailablefornon-electricheatunits,inlieuofsingle-uselters.
Single-use lters feature Amerglas media. They are designed to
be used once and discarded.
Permanent lters aremetalltersthatmayberemovedforcleaning
and reused numerous times.
Renewable media lters(gure134)consistofaheavypainted
metal structural frame and renewable Amerglas media.
Turn off unit before servicing to avoid danger of injury from
rotating fans.
Dirty or clogged lters can impact unit performance, resulting
in damage to the unit.
12" Left Front
Access Panel
Motor
12" Right Front Access Panel
Top Access
Doors
Figure 136 - Filter installation
Complete Check, Test and Start
Procedure
(Included in the shipping envelope in the end compartment of
the unit). Provide completed Check, Test and Start procedure to local
Daikin representative and to specifying engineer to verify proper start-
up was completed.
Electric heat units should ONLY use permanent wire mesh
lters. Filters other than wire mesh are not intended for electric
heat units, and can cause unit damage, property damage or
personal injury.
Filter
Renewable Media (Single-use and
Permanent Wire Mesh Filters Also Available)
Structural
Frame
Installer/Owners Responsibility
Protect your investment - read carefully
Your Daikin express written limited warranty does not cover
equipment failures that are caused by misuse, abuse, mis-installation,
failure to maintain the unit, etc. So, for example, the following
damage is not covered by warranty:
1. Progressive damage to machine from failure to check and test at
start-up.
2. Damage resulting from handling during installation or damage
resulting from transportation.
3. Incorrectoructuatingpowersupply.
4. Damage resulting from failure to keep evaporator coil and intake
clean.
5. Damage resulting from freezing water or condensate, inadequate
or interrupted water supply, use of corrosive water, rearrangement
of unit piping system, fouling or restriction of the water circuit by
foreign material.
6. Inaccessibility of unit for service or parts installation that prevents
proper equipment operation.
7. Damage resulting from the use of the unit in a corrosive atmosphere,
ie., cleaning materials, fumes, etc
8. Damagecausedbynotcleaningorreplacinglters.
9. Damage caused by accident, alteration of unit design, or
tampering.
Please complete and return the Check, Test and Start document
immediately to protect your warranty.