Actuator Type
Power Power Transformer
Torque
Running
Direction of Rotation
Supply Consumption Sizing Time
Outdoor Air/Return Air
24 VAC ±20% 4 VA 80 to 110 sec Reversible with built in switch L/R
Damper Actuator
50/60 HZ 2 Watts (class 2 power source) 45 in-lb for 0 to 35 in-lb L = CW with an increase in voltage.
24 VDC ±10%
R = CCW with an increase in voltage.
Spring: reversible with CW/CCW
Face & Bypass
24 VAC ±20%
Running: 2.5 Watt;
5 VA 90 sec constant mounting.
50/60 HZ Holding: 1 Watt (class 2 power source) 45 in-lb
(independent
Motor: reversible with built in switch.
Damper Actuator
24 VDC ±10%
of load)
CW = CW with a decrease in signal.
CCW = CCW with a decrease in signal.
Figure 114 - Sensor Locations
Discharge Air Sensor
Room Air Sensor
Holes in Front
Access Panel
Outdoor Air Sensors
Outdoor Air
Opening
based on a 2 to 10 VDC input from the DDC Unit Ventilator Controller
(UVC).A4to20mAinputsignalcanbeusedwiththeeldadditionof
a Belimo ZG-R01 (or equivalent) 500 ohm resistor (by others). Refer to
the wiring diagram for proper installation of the resistor. A 2 to 10 VDC
output signal is provided for damper position feedback. The gears can
be manually disengaged with a button on the actuator cover. Rotation
is counterclockwise to bypass air around coil.
The outdoor air/return air damper actuator is a unit mounted, direct
coupled, proportional control actuator that spring returns the outdoor
air damper shut upon a loss of power. The actuator provides proportional
damper control based on a 2 to 10 VDC input from the DDC Unit
Ventilator Controller (UVC). A 4 to 20 mA input signal can be used with
theeldadditionofaBelimoZG-R01(orequivalent)500ohmresistor
(by others). Refer to the wiring diagram for proper installation of the
resistor. A 2 to 10 VDC output signal is provided for damper position
feedback. Rotation is clockwise to open OA, close RA.
Face and Bypass Damper Actuator
The Face & Bypass damper actuator is a unit mounted, direct coupled,
non-spring returned actuator used for the modulation of the face and
bypass damper. The actuator provides proportional damper control
A10KohmNegativeTemperatureCoefcient(NTC)sensoranda
1KohmPositiveTemperatureCoefcientsensorisprovidedforthe
discharge air, outdoor air and room air temperature measurement. They
are located next to each other in the air stream as shown in Figure 114.
Each is wired to the terminal strip separately so that the Automatic
Temperature Control contractor may select the appropriate sensor for
the application.
10 K ohm NTC Sensor
The 10 K ohm NTC sensor is constructed from stainless steel with an
epoxy seal and twisted wire leads.
Type:
10K ohm @ 25ºC
Accuracy: ±0.2ºF, 40
o
F - 80ºF
±0.36ºF, 32ºF - 158ºF
1 K ohm PTC Sensor
The 1 K ohm sensor is a shrink-wrap encapsulated, PTC silicon sensing
element with stranded, tinned copper wire leads (#22 AWG).
Type:
1035 ohm @ 25ºC
Accuracy: ±0.9ºF, 5ºF - 167ºF
Digital Ready Unit Mounted
Temperature Sensor Specications
Table 27. - Actuators Technical Data
Table 26 - Temperature Sensors Resistance Values
Digital Ready – Damper Actuator
Specications
Outdoor Air/Return Air Damper Actuator
Figure 115 - Outdoor Air/Return Air Damper Actuator & Face
and Bypass Damper Actuator
Temperature (ºC) -40 -20 0 20 25 30 40 50 60
10 K ohm (NTC)
Resistance (ohms) 337200 97130 32660 12490 10000 8056 5326 3602 2489
1 K ohm (PTC)
Temperature (ºC) -40 -20 0 20 25 30 40 50 60
Resistance (ohms) 613 727 855 997 1035 1074 1153 1237 1323