98
• Control systems
• intelligent Touch Manager • ED721208
4.2. Dio Unit <DEC102A51>
Using this unit, connection of other facilities other than air conditioner is made possible, such as power supply facility, sanitary facility,
anti-disaster facility, and crime prevention facility.
Function
Type BRC1C62 DEC102A51
Group/Zone
Item
One Group Up to 4 groups
ON/OFF Possible Possible
Temp. setting Possible Impossible
Airflow rate setting Possible Impossible
Airflow direction setting Possible Impossible
Timer setting twice a day Possible Impossible
Mode setting Possible Impossible
Filter sign reset Possible Impossible
Inspection/Test operation Possible Operation & Error display only by lamps
• Dio Unit (DEC102A51)
L·N
F1·F2
D·CD
M·CM
A·CA
Centralized control equipment
Operation output
5
Dio unit
Power supply
200 - 240 V
To other Di/Dio unit
Operating status input
5
Error status input
5
Max.4unitsof
facilityequipment