Installation condition check
Normal
Check the
allowable
dimensions of the air
suction and discharge area.
Is the
airflow blocked by
obstacles or winds blowing
in the opposite direction?
(R9459)
Abnormal
YES
YES
YES
Is the
discharged air
short-circuited?
NO
NO
NO
Is the outdoor
heat exchanger very dirty?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the outdoor temperature.
(The outdoor temperature
should be 46°C or lower.)