SiENBE04-808_A Control Specification
Function and Control 60
3.13 Forced Operation Mode
Outline Forced operation mode includes only forced cooling.
Detail
3.14 Standby Electricity Saving
20-42 Class Only
This function turns power supply OFF to the outdoor unit and sets the indoor unit into energy-
saving mode, thus reducing the power consumption of the air conditioner.
For 20/25/35 class models, field setting is required for turning ON the function.
Refer to “Standby Electricity Saving” on page 290 for detail.
Item Forced Cooling
Conditions 1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced operation is allowed when the above both conditions are met.
Start 1) Press the forced operation ON/OFF button (SW1) on the indoor unit for 5
seconds.
2) Press the forced operation ON/OFF button (SW1) on the outdoor unit.
Command
frequency
RK(X)S20-35G2V1B, ARXS20-35G2V1B: 68 Hz
RK(X)S20-35G2V1B9, ARXS20-35G3V1B: 58 Hz
RK(X)S42G2V1B, ARXS42G2V1B: 47 Hz
RK(X)S50G2V1B, ARXS50G2V1B: 66 Hz
End 1) The operation ends automatically after 15 minutes.
2) Press the forced operation ON/OFF button (SW1) on the indoor unit again.
3) Press the ON/OFF button on the remote control.
4) Press the forced operation ON/OFF button (SW1) on the outdoor unit.
Others The protection functions are prior to all others in the forced operation.
SiENBE04-808_A.pdf 72 21/02/2011 13:19:57