EasyManua.ls Logo

Daikin FTXS20G2V1B - Thermostat Control

Daikin FTXS20G2V1B
316 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiENBE04-808_A Main Functions
Function and Control 36
1.6 Thermostat Control
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Heating
B
A
OFF
OFF
ON
C
Room thermistor temperature – target temperature
–1.5°C
(R12319)
Cooling : –0.5°C
Dry : –0.5°C
Cooling : –2.0°C
Dry : –2.5 ~ –2.0°C
B
A
OFF
ON
ON
C
1.5°C
1.0°C
Room thermistor temperature – target temperature
0°C
(R12320)
SiENBE04-808_A.pdf 48 21/02/2011 13:19:56

Table of Contents

Other manuals for Daikin FTXS20G2V1B

Related product manuals