SiENBE04-808_A Control Specification
Function and Control 48
3.3 Controls at Mode Changing / Start-up
3.3.1 Preheating Operation
Outline The inverter operation in open phase starts with the conditions of the preheating command from
the indoor unit, the outdoor temperature, and the discharge pipe temperature.
Detail RK(X)S20-42G2V1B, ARXS20-42G2V1B
ON Condition
When the discharge pipe temperature is below 10ºC, the inverter operation in open phase
starts.
OFF Condition
When the discharge pipe temperature is higher than 12ºC, the inverter operation in open
phase stops.
RK(X)S20-35G2V1B9, ARXS20-35G3V1B
Outdoor temperature 7°C Control A
Outdoor temperature < 7°C Control B
Control A
ON condition
Discharge pipe temperature < 10°C
OFF condition
Discharge pipe temperature > 12°C
Radiation fin temperature 90°C
Control B
ON condition
Discharge pipe temperature < 20°C
OFF condition
Discharge pipe temperature > 22°C
Radiation fin temperature 90°C
RK(X)S50G2V1B, ARXS50G2V1B
Outdoor temperature 10°C Control A
Outdoor temperature < 10°C Control B
Control A
ON condition
Discharge pipe temperature < 6°C
OFF condition
Discharge pipe temperature > 8°C
Radiation fin temperature 90°C
Control B
ON condition
Discharge pipe temperature < 10.5°C
OFF condition
Discharge pipe temperature > 12°C
Radiation fin temperature 90°C
SiENBE04-808_A.pdf 60 21/02/2011 13:19:56