SiENBE04-808_A Outdoor Unit - RK(X)S42G2V1B, ARXS42G2V1B
Removal Procedure 242
6
Disconnect the
connector for the
overload protector
[S40].
7
Disconnect the
connector for the
electronic expansion
valve coil [S20].
8
Disconnect the
connector for the four
way valve coil [S80].
9
Disconnect the
connector for the
thermistors [S90].
Step
Procedure Points
(R0255)
[S40]
(R0256)
[S20]
(R0257)
[S80]
(R0258)
[S90]
SiENBE04-808_A.pdf 254 21/02/2011 13:20:19