SiENBE04-808_A Outdoor Unit - RK(X)S42G2V1B, ARXS42G2V1B
Removal Procedure 260
4
Remove the protection
bushing.
5
Remove the 2 nuts of
the compressor.
Warning
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas brazing machine.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (If the refrigerant gas is
exposed to flames, toxic gas
may be generated.)
Warning
Since it may happen that the
refrigerant oil in the
compressor catches fire,
prepare wet cloth so as to
extinguish fire immediately.
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to collect all the
refrigerant gas.
Before working, make
sure that the refrigerant
gas is empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
6
Heat up the brazed part
of the discharge side
and disconnect.
7
Heat up the brazed part
of the suction side and
disconnect.
Step
Procedure Points
(R8199)
Protection bushing
U
W
V
(R0265)
(R8201)
SiENBE04-808_A.pdf 272 21/02/2011 13:20:22