Overview of the cooling mode functions ESIE02–01
2–28 Part 2 – Functional Description
3
1
2
4
5
Integral capacity The illustration below shows the integral capacity in function of the compressor running time.
Mode 0 Intelligent control mode
When the DIP switches are in mode 0, “intelligent freeze-up prevention control” determines the
freeze-up activation. The outdoor unit can determine the freeze-up activation.
Mode 1 Disabled intelligent control mode
The table below contains the freeze-up conditions, these are the same as for the Sky Air G- and
K-series.
Mode 2 Added countermeasure to avoid ice/water blow out during freeze-up cycle.
Mode 2 enables the possibility to start a freeze-up activation decision by the outdoor unit, but with
more severe conditions than in mode 0.
Mode 3 Mode 3 is used in case mode 2 is insufficient as countermeasure.
Integral
capacity
Cooling or dry keep
Freeze-up operation
Diminishing
integral capacity
Max. integral
capacity value
Compr. ON time
Condition
(OR)
Evap. temp. Timers Remarks
1-1˚C 40 min compressor accumu-
lated time
2-3˚CTe -3˚C for 1 min continu-
ously after minimum 8 min of
operation
Only for FHYP
3-5˚CTe -5˚C for 1 min continu-
ously after minimum 8 min of
operation
For indoor units other than FHYP
Model Used in case of...
FAYReverse angle installation for water drain flow.
4-way cassette 2- or 3-way air outlet.