ESIE02–01 Overview of the cooling mode functions
Part 2 – Functional Description 2–29
3
2
4
5
1
Ending condition The table below contains the freeze-up operation ending conditions.
Heating operation
during freeze-up
Heating operation activation during freeze-up activation is possible.
In case of... The freeze-up operation is ended when...
Mode 0, 2 or 3 Te > +10˚C for 10 min continuously
Mode 1 Te > +7˚C for 10 min continuously