EasyManua.ls Logo

Daikin VHF - Fan Performance for Constant Torque EC Motor (Sizes 009-012)

Daikin VHF
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PerforManCe
Fan Speed Selector Switch
A 4-position fan speed selector switch located in the control
box allows CFM settings to be eld adjustable. Fan speed
control optimizes unit fan speed based on thermostat/room
sensor inputs. The fan speed switch allows for manually setting
an optimal fan speed specic to the application requirements.
Refer to Table 4
Figure 55: 4-position fan speed selector switch
Fan Performance for Constant Torque EC Motor (Sizes 009-012)
Table 20: Constant torque EC motor CFM values
Unit Size Setting Function
External Static Pressure (in-H
2
O) [Dry Coil and STD Filter) (inches of water column)
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40
009
4 (High)
Stage 1
430 410 390 370 350 340 320 300 280
3 (Standard) 420 400 380 360 340 320 300 270 250
2 (Medium) 350 330 310 290 270 250 230 210 190
1 (Low) 350 330 310 290 270 250 230 210 190
4 (High)
Stage 2
450 430 410 400 380 360 340 320 300
3 (Standard) 430 410 390 370 350 340 320 300 280
2 (Medium) 420 400 380 360 340 320 300 270 250
1 (Low) 350 330 310 290 270 250 230 210 190
4 (High)
Fan Only
350 330 310 290 270 250 230 210 190
3 (Standard) 350 330 310 290 270 250 230 210 190
2 (Medium) 370 340 310 280 250 220 190 160 130
1 (Low) 370 340 310 280 250 220 190 160 130
4 (High)
Hydronic
Heat
430 410 390 370 350 340 320 300 280
3 (Standard) 420 400 380 360 340 320 300 270 250
2 (Medium) 350 330 310 290 270 250 230 210 190
1 (Low) 370 340 310 280 250 220 190 160 130
012
4 (High)
Stage 1
450 430 410 390 370 340 320 300 280
3 (Standard) 420 400 380 360 340 310 290 270 250
2 (Medium) 400 370 350 330 310 290 260 240 220
1 (Low) 400 370 350 330 310 290 260 240 220
4 (High)
Stage 2
470 450 430 410 390 370 350 330 310
3 (Standard) 450 430 410 390 370 340 320 300 280
2 (Medium) 420 400 380 360 340 310 290 270 250
1 (Low) 400 370 350 330 310 290 260 240 220
4 (High)
Fan Only
400 370 350 330 310 290 260 240 220
3 (Standard) 400 370 350 330 310 290 260 240 220
2 (Medium) 360 330 300 270 240 210 180 150 120
1 (Low) 360 330 300 270 240 210 180 150 120
4 (High)
Hydronic
Heat
450 430 410 390 370 340 320 300 280
3 (Standard) 420 400 380 360 340 310 290 270 250
2 (Medium) 400 370 350 330 310 290 260 240 220
1 (Low) 360 330 300 270 240 210 180 150 120
Note: 1. EC motor is programmed to make soft starts and stops to reduce stress transmitted to the fan housing. They adjust their speed and torque to deliver constant
airow over a wide range of external static pressure.
2. Units are shipped at setting 3 (standard). Speed adjustment is done by 4-position switch in the control box.
3. The unit is capable of high-low fan performance through the use of a 2-stage thermostat wired to specic terminals for
High-Low CFM fan performance. Standard operation with a 1-stage thermostat is indicated as stage 2 fan performance.
www.DaikinApplied.com 45 Vertical Stack WSHP • IM 986-11

Table of Contents

Related product manuals