Field Settings for Indoor Unit SiAF332111E
98 Part 5 Field Settings and Test Operation
When the unit is equipped with an infrared presence/floor sensor:
: Factory setting
Refer to Compensating the temperature around people.
Note that the control is automatically switched to the one performed only by the suction air
thermistor for indoor unit when the Second code No. is 01 during the group control.
To use the remote controller thermistor during the group control, select the Second code No. 02
in First code No. 6.
1.4.3 Filter Cleaning Sign
Whether or not to display the sign after operation of a certain duration can be selected.
: Factory setting
1.4.4 Information for intelligent Touch Manager / intelligent Touch
Controller
: Factory setting
When field setting 10 (20)-6-02 is set at the same time as 10 (20)-2-01,02,03, field setting 10
(20)-2 has priority. When field setting 10 (20)-6-01 is set at the same time as 10
(20)-2-01,02,03, field setting 10 (20)-6 has priority for group connection, and 10 (20)-2 has
priority for individual connection.
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20) 6
01
Remote controller thermistor control is not permitted during
group control
02
Remote controller thermistor control is permitted during group
control
Mode No. Second Code No.
10 (20) 2 01 02 02 02 02 03
11 (21) 8 01 01 02 03 04 01
The thermistor to be used
Remote controller thermistor
———
—
Suction air thermistor
—
Infrared floor sensor — — —
First Code No.
The infrared floor
sensor is not used
Priority given to
the suction air
temperature ()
Only the remote
controller thermistor
is used
Priority given to the
floor temperature ()
Only the suction air
thermistor is used
Standard setting
(Factory setting)
Mode
No.
First Code
No.
Second
Code No.
Contents
10 (20) 3
01
Displayed
02 Not displayed
Mode
No.
First Code
No.
Second
Code No.
Contents
10 (20) 5
01
Only indoor unit sensor value (or remote controller sensor
value, if installed.)
02 Sensor values according to 10 (20)-2 and 10 (20)-6.