EasyManua.ls Logo

Daikin VRV S RXQ4/5ARV1 - Check Operation; Setting of Vacuuming Mode

Daikin VRV S RXQ4/5ARV1
377 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiAF332111E Field Settings for Outdoor Unit (4/5 HP Models)
Part 5 Field Settings and Test Operation 121
2.6 Setting of Vacuuming Mode
In order to perform vacuuming operation on site, fully open the electronic expansion valves of
indoor and outdoor units and turn on some solenoid valves.
Operating procedure
1. While the outdoor unit is not operating, set the item 2-21 (refrigerant recovery/vacuuming
mode) to ON.
The respective expansion valve of indoor and outdoor units are fully opened. Test
Operation and Under Centralized Control are displayed on the remote controller, and the
indoor/outdoor unit operation is prohibited.
After setting, do not cancel setting mode 2 until completion of Vacuuming operation.
2. Use the vacuum pump to perform vacuuming operation.
3. Press the MODE (BS1) button once and reset setting mode 2.
2.7 Check Operation
To prevent any trouble in the period of installation onsite, the system is provided with a test
operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or
misplacing with suction pipe thermistor) or discharge pipe thermistor and judgment of piping
length, refrigerant overcharging, and learning for the minimum opening degree of electronic
expansion valve.
Unit stopping
Press the TEST (BS4) button for
5 seconds.
10 seconds to 10 minutes
LED display (H1P~H7P) (
k: ON h: OFF l: BLINK)
hhkhhhh
hlhhhhk
Pressure equalizing
Step 1
20 seconds to 2 minutes
10 minutes
3 minutes
15 minutes
hlhhhkh
Cooling start controlStep 2
hlhhhkk
hlhhkkk
Stability waiting operationStep 3
Refrigerant overcharge judgment
Step 7
Stop valve close check
Wrong wiring check
Piping length check
hlhhkhh
hlhhkhk
hlhhkkh
Judgment function
Step4~6
5 seconds
hlhkhhk
hlhkhkh
Pump down residual control
Step 8
2 minutes
Standby for restarting
Completion
Step 9

Table of Contents