Address Setting for Wireless Remote Controller SiAF332111E
46 Part 3 Remote Controller
4.2 Setting for BRC4M Series
The address for the wireless remote controller is set to 1 at the factory. To change the setting,
proceed as follows:
1. Press the FILTER SIGN RESET button and the INSPECTION button for at least 4 seconds
to enter the Field Setting mode.
(SETTING is indicated on the display.)
2. Press the SELECT button and select a multiple setting (A/b). Each time the button is
pressed the display switches between A and b.
3. Press the TEMP buttons to set the address.
Address can be set from 1 to 6, but set it to 1-3 and to the same address as the receiver.
(The receiver does not work with address 4-6.)
4. When the RESERVE button is pressed, the setting is confirmed and the usual display
returns.
Address
Multiple setting
1
4
2
3