SiAF332111E Check
Part 6 Service Diagnosis 355
6.14 Master-Slave Unit Setting Table
CHECK 14 Combination of intelligent Touch Controller and Central Remote Controller
CRC (Central remote controller): DCS302CA61
intelligent Touch Controller: DCS601C51
The patterns marked with have nothing to do with those described in the list of setting of
master unit centralized setting connector.
6.15 Broken Wire Check of the Relay Wires
CHECK 15 Procedure for checking indoor-outdoor unit transmission wiring for broken wires
Turn OFF the power supply to all equipment, short circuit between the indoor-outdoor unit
terminal F1 and F2 in outdoor unit, and then conduct continuity checks between the
transmission wiring F1 and F2 of "Indoor Unit a" farthest from outdoor unit using a multimeter. If
there is continuity between the transmission wiring, the indoor-outdoor unit transmission wiring
has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the indoor-outdoor
unit terminal of outdoor unit short circuited, identify the areas with continuity in the transmission
wiring of "Indoor Unit b", transmission wiring of "Indoor Unit c", and transmission wiring of
"Indoor Unit d" in the order described.
If the areas with continuity can be identified, there may be broken wires in places before those
areas.
Pattern
#1 #2 #3 #4
1-00~4-15
Master/
Slave
5-00~8-15
Master/
Slave
1-00~4-15
Master/
Slave
5-00~8-15
Master/
Slave
(1) CRC Master CRC Master CRC Slave CRC Slave
(2) CRC Master — — CRC Slave — —
(3)
intelligent
Touch
Controller
Master — —
intelligent
Touch
Controller
Slave — —
(4) CRC Master — —
intelligent
Touch
Controller
Slave — —
(5)
intelligent
Touch
Controller
Master — — CRC Slave — —
(6) CRC Master — — — — — —
(7)
intelligent
Touch
Controller
Master — — — — — —
Check the transmission
a b c d
wiring for continuity.
If there is continuity, the
indoor-outdoor unit
transmission has no
broken wires in it.
Indoor-outdoor Unit
Transmission Wiring
Short circuit between
the indoor-outdoor unit
terminal parts.
Outdoor
unit