Troubleshooting by Error Code SiAF332111E
224 Part 6 Service Diagnosis
5.20 Infrared Presence/Floor Sensor Error
Applicable
Models
FXFSQ-AR
Error Code CE
Method of Error
Detection
The contents of a failure vary with the detailed error code. Check the code and proceed with the
flowchart.
Error Decision
Conditions
Error is detected based on sensor output signals
Supposed
Causes
Defective or disconnected infrared presence sensor connector: CE-01
Defective infrared floor sensor (Temperature compensation circuit disconnection): CE-02
Defective infrared floor sensor (Temperature compensation short circuit): CE-03
Defective infrared floor sensor element: CE-04
Troubleshooting
See diagnosis procedure 2.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Error code
CE-02
See diagnosis procedure 3.
Error code
CE-03
See diagnosis procedure 4.
Error code
CE-04
Error type varies according
to error code. Check the
error code and take the
following steps.
See diagnosis procedure 1.
Error code
CE-01