Field Settings for Indoor Unit SiAF332111E
94 Part 5 Field Settings and Test Operation
1.2 List of Field Settings for Indoor Unit
: Factory setting
Mode
No.
(2)
First
Code
No.
Description
Second Code No.
Reference
Page
01 02 03 04
10 (20)
0
Filter
cleaning
sign interval
Ultra long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
——97
Long life filter Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard filter Approx.
200
hrs.
Approx.
100 hrs.
1
Filter type
Long life filter
Ultra long life
filter
——97
2
Remote controller thermistor Remote
controller
thermistor +
Suction air
thermistor
Only suction air
thermistor
Only remote
controller
thermistor
—97
3 Filter cleaning sign Displayed
Not displayed 98
5
Information for intelligent Touch
Manager / intelligent Touch
Controller
Refer to the page on the right for details. 98
6
Remote controller thermistor
control during group control
Not permitted
Permitted 97
7
Time for absence area
detection
30 minutes 60 minutes 99
10
Dry operation time during
VRTsmart control 30 minutes
60 minutes 90 minutes
Continuous
(not returning
to cooling)
99
11
Low airflow setting when
thermostat OFF during
VRTsmart control
Disabled Enabled ——99
11 (21)
6
Setting the rate of human
detection
High sensitivity Low sensitivity
Standard
sensitivity
Infrared
presence
sensor
disabled
100
7
Automatic airflow adjustment
OFF
Completion of
airflow
adjustment
Start of
airflow
adjustment
—100
8
Compensating the temperature
around people
Suction air
temperature only
Priority given on
the suction air
temperature
Standard
Priority given
on the floor
temperature
101
12 (22)
0
Optional accessories output
selection
Indoor unit
turned ON by
thermostat
Operation
output
Error output 101
1
External ON/OFF input
Forced OFF
ON/OFF control
External
protection
device input
—101
2
Thermostat differential
changeover
1°C
0.5°C 102
5 Auto restart after power failure OFF ON
——102
6
Airflow setting when cooling
thermostat is OFF
LL tap Set fan speed
——102
11
Compensating the floor
temperature when cooling
4°C 2°C 0°C
–2°C 102