EasyManua.ls Logo

Daikin VRV S RXQ4/5ARV1 - Page 108

Daikin VRV S RXQ4/5ARV1
377 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Field Settings for Indoor Unit SiAF332111E
102 Part 5 Field Settings and Test Operation
1.4.13 Thermostat Differential Changeover
Set when remote sensor is to be used.
Differential value during thermostat ON/OFF control can be changed.
: Factory setting
1.4.14 Auto Restart after Power Failure
: Factory setting
When the "Auto Restart after Power Failure" setting is turned OFF, all the units will remain OFF
after power failure, or after the main power supply is restored. When this setting is turned ON
(factory setting), the units that were operating before the power failure will automatically restart
operation after power failure, or after the main power supply is restored.
Due to the aforementioned, when the "Auto restart after power failure” setting is ON, be careful
for the following situations that may occur.
1.4.15 Airflow Setting when Cooling Thermostat is OFF
This is used to set airflow to LL airflow when cooling thermostat is OFF.
: Factory setting
1.4.16 Compensating the Floor Temperature when Cooling
Offset the detected value of the infrared floor sensor with a certain temperature. This setting
should be used to have the actual floor temperature detected when, for example, the unit is
installed close to a wall.
: Factory setting
Specific usages of this setting
There is no problem with the standard setting in the usual condition. Change the setting in the
cases indicated in the following table.
Mode
No.
First Code
No.
Second
Code No.
Contents
12 (22) 2
01
1ºC
02 0.5ºC
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22) 5
01 OFF
02
ON
1. The air conditioner will start operation suddenly after power failure,
or when the main power supply is restored. The user might be surprised
and wonder why the air conditioner turned ON suddenly.
2. During maintenance, if the main power supply is turned OFF while the
units are in operation, the units will automatically start operation
(the fan will rotate) after the power supply is restored due to completion
of the maintenance work.
Caution
Mode
No.
First Code
No.
Second Code
No.
Contents
12 (22) 6
01 LL tap
02
Set fan speed
Mode
No.
First Code
No.
Second Code
No.
Contents
12 (22) 11
01 +4°C
02 +2°C
03
0°C
04 –2°C

Table of Contents

Related product manuals