EasyManua.ls Logo

Daikin VRV S RXQ4/5ARV1 - Radiation Fin Temperature Abnormality

Daikin VRV S RXQ4/5ARV1
377 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiAF332111E Troubleshooting by Error Code
Part 6 Service Diagnosis 289
5.52 Radiation Fin Temperature Abnormality
Applicable
Models
RXQ4/5AR, RXMQ6/8AR
Error Code P4
Method of Error
Detection
Detect the resistance of the following thermistors during the compressor stops running:
(1) Radiation fin thermistor
(2) Thermistor located in PCB circuit
Error Decision
Conditions
When the resistance of the thermistor comes to a value equivalent to open or short circuit.
Error is not decided while the unit operation is continued.
P4 will be displayed by pressing the inspection button.
Supposed
Causes
Defective radiation fin temperature thermistor
Defective outdoor unit main PCB (RXQ4/5AR, RXMQ6AR)
Defective inverter PCB (RXMQ8AR)
Defective fan PCB (RXMQ8AR)
Defective compressor
Defective fan motor