Outline of Control (Indoor Unit) SiAF332111E
82 Part 4 Functions and Control
3.4 Airflow Direction Control
3.4.1 Without Optional Infrared Floor Sensor
Refer to the table below for controlling the horizontal flap (or the vertical flap) for airflow direction
adjustment.
3.4.2 With Optional Infrared Floor Sensor
The model can control airflow direction automatically by the difference between suction air
temperature and floor temperature.
Operation in auto airflow direction control when cooling
H
HM
M
ML
L
Fan tap
LargeDifference between control target Small
temperature and set temperature
<Change in airflow rate under
automatic airflow rate control>
Except for FXFSQ-AR,
HM and ML taps appear
only during the auto
airflow rate control
operation.
(For FXFSQ-AR,
HM and ML taps can be
manually set with remote
controller.)
Conditions FXAQ-P
Cooling Direction set Thermostat ON Set
Thermostat OFF Set
Swing set Thermostat ON Swing
Thermostat OFF Swing
Program dry Direction set Thermostat ON Set
Thermostat OFF Set
Swing set Thermostat ON Swing
Thermostat OFF Swing
Fan Direction set Set
Swing set Swing
Conditions
FXFSQ-AR
When airflow direction is set
Automatic airflow rate and eco
full automatic control
Cooling Direction set Thermostat ON Set Automatic (P0 or P1)
Thermostat OFF Set Automatic (P0 or P1)
Swing set Thermostat ON Swing
Thermostat OFF Swing
Program dry Direction set Thermostat ON Set Automatic (P0 or P1)
Thermostat OFF Set Automatic (P0 or P1)
Swing set Thermostat ON Swing
Thermostat OFF Swing
Fan Direction set Set Horizontal (P0)
Swing set Swing
P1
P0 (Horizontal)
The difference between suction air
and floor temperatures is small.
The difference between suction air
and floor temperatures is large.