SiAF332111E Capacity Range
Part 1 General Information 11
3. Capacity Range
3.1 Connection Ratio
3.2 Outdoor Unit Combinations
Type Min. connection ratio Max. connection ratio
Single outdoor units 50% 130%
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Model RXQ4ARV1 RXQ5ARV1 RXMQ6ARV1 RXMQ8ARY1 RXMQ10ARY1 RXMQ12ARY1
kW 11.2 14.0 16.0 22.4 28.0 33.5
HP 45681012
Capacity index 100 125 150 200 250 300
Total capacity
index of
connectable
indoor units
Combination (%) 50% 50 62.5 75 100 125 150
100% 100 125 150 200 250 300
130% 130 162.5 195 260 325 390
Maximum number of connectable indoor
units
6 8 9 13 16 19