EasyManua.ls Logo

Daikin VRV S RXQ4/5ARV1 - Power Supply Insufficient or Instantaneous Abnormality

Daikin VRV S RXQ4/5ARV1
377 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiAF332111E Troubleshooting by Error Code
Part 6 Service Diagnosis 299
5.58 Power Supply Insufficient or Instantaneous Abnormality
5.58.1 Power Supply Insufficient or Instantaneous Abnormality (4/5 HP
Models)
Applicable
Models
RXQ4/5AR
Error Code U2
Method of Error
Detection
The main circuit capacitor voltage of the inverter and the power supply voltage is checked.
Error Decision
Conditions
The main circuit capacitor of the tested inverter has abnormal voltage or the power supply
voltage is abnormal.
Supposed
Causes
Insufficient power supply
Instantaneous power failure
Defective outdoor fan motor
Defective outdoor unit main PCB