SiAF332111E Troubleshooting by Error Code
Part 6 Service Diagnosis 331
5.73 Operation Lamp Blinking
Applicable
Models
ON/OFF controller
Indoor unit
Error Code
Method of Error
Detection
DIII-NET communication data is used to detect the error.
Error Decision
Conditions
Supposed
Causes
Defective transmission between the centralized controller and an indoor unit
Loosened setting connector of the main centralized controller
Defective ON/OFF controller PCB
Defective indoor unit PCB
Defective air conditioner
Troubleshooting
NO
YES
NO
NO
YES
YES
YES
Perform troubleshooting
using the air conditioner
troubleshooting.
Concurrently reset the
power supply of all the
centralized controllers.
Turn on the power of the indoor unit.
Correct the wiring.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are
there any error
codes displayed on the
remote controller?
Is the
connection
wiring broken or
wrong?
Are any
connected
indoor units removed or
the control range
setting changed?
Is
the power
of the indoor unit
displaying the error
turned on?
NO
Go to the next page.
A