Troubleshooting by Error Code SiAF332111E
332 Part 6 Service Diagnosis
NO
NO
YES
YES
YES
NO
YES
NO
Correct the setting of
the group No.
Correct the wiring.
ON/OFF controller
Connect the connector
correctly.
Replace the centralized
controller PCB.
Are
all the indoor
units experiencing
transmission
failure?
Does
the indoor unit
on which the error occurred
set the group No.?
Is the setting
connector of the main
centralized controller
loose?
Is the
main centralized
controller connection
wiring broken or
wrong?
A