1.4 Details of Field Settings for Indoor Unit
1.4.1 Filter Cleaning Sign Interval, Filter Type
When the setting 10 (20)-3 is set to 01 (Displayed), filter cleaning sign is displayed on the
remote controller after a certain period of operation time. This setting is used to change the
display interval of filter cleaning sign when the filter contamination is heavy.
The filter cleaning sign interval is determined as follows depending on the combination of Mode
No. 10 (20)-0 and 10 (20)-1.
Filter cleaning sign interval
: Factory setting
1.4.2 Remote Controller Thermistor
Select a thermistor to control the room temperature.
When the unit is not equipped with an infrared floor sensor:
: Factory setting
The factory setting for the Second code No. is 01 and room temperature is controlled by the
suction air thermistor for indoor unit and remote controller thermistor. When the Second code
No. is set to 02, room temperature is controlled by the suction air thermistor. When the Second
code No. is set to 03, room temperature is controlled by the remote controller thermistor.
Setting
10 (20)-1 01: Long life filter
02: Ultra long life filter
Filter contamination
heavy/light 10 (20)-0
Light
01
Heavy
02
Light
01
Heavy
02
Model
FXFSQ-AR
2,500 hrs.
1,250 hrs. 10,000 hrs. 5,000 hrs.
FXMQ-PB
FXMQ-AR
FXAQ-P 200 hrs.
100 hrs. 200 hrs. 100 hrs.
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20) 2
01
Remote controller thermistor and suction air thermistor
in indoor unit
02 Suction air thermistor in indoor unit
03 Remote controller thermistor
20
22
24
26
28
30
32
34
36
211917 23 25 27 29 31 33 35 37
In cooling
Suction air temperature (˚C)
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Remote controller
thermistor
Remote controller
thermistor
Set temperature (˚C)