SiAF332111E Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation 103
1.4.17 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height.
FXFSQ25-80AR
: Factory setting
FXFSQ100-140AR
: Factory setting
1. The Second Code No. is factory set to Standard/All-direction airflow. For High ceiling (1) or
(2), initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
FXFSQ-AR with Designer panel
: Factory setting
FXAQ-P
: Factory setting
Environment
Operation
Mode
Problem Setting Value
- The unit is installed close to a wall or a window.
- High thermal capacity of the floor (such as concrete,
etc.).
- There are many heat sources including PC.
- There is a non-negligible heat source such as floor
heating.
Cooling
Insufficient
cooling
+2°C or +4°C
Excessive
cooling
–2°C
Mode
No.
First
Code No.
Second
Code No.
Contents
Ceiling Height
All round
outlet
4-way
Outlets
3-way
Outlets
2-way
Outlets
13
(23)
0
01
Standard
Lower
than
2.7 m
Lower
than
3.1 m
Lower than
3.0 m
Lower than
3.5 m
02
High
Ceiling(1)
Lower than
3.0 m
Lower than
3.4 m
Lower than
3.3 m
Lower than
3.8 m
03
High
Ceiling(2)
Lower than
3.5 m
Lower than
4.0 m
Lower than
3.5 m
—
Mode
No.
First
Code No.
Second
Code No.
Contents
Ceiling Height
All round
outlet
4-way
Outlets
3-way
Outlets
2-way
Outlets
13
(23)
0
01
Standard
Lower
than
3.2 m
Lower
than
3.4 m
Lower than
3.6 m
Lower than
4.2 m
02
High
Ceiling(1)
Lower than
3.6 m
Lower than
3.9 m
Lower than
4.0 m
Lower than
4.2 m
03
High
Ceiling(2)
Lower than
4.2 m
Lower than
4.5 m
Lower than
4.2 m
—
Mode
No.
First
Code
No.
Second
Code No.
Contents
FXFSQ25-80AR
(All round outlet)
FXFSQ100-140AR
(All round outlet)
13
(23)
0
01
Standard
Lower than
2.4 m
Lower than
3.2 m
02 High Ceiling (1)
Lower than
2.7 m
Lower than
3.6 m
03 High Ceiling (2)
Lower than
3.2 m
Lower than
4.2 m
Mode
No.
First Code
No.
Second
Code No.
Contents
13 (23) 0
01
Standard
02 Slightly higher
03 High