SiAF332111E Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation 93
1.1.2 BRC4M Series
Setting
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
To change the field settings, proceed as follows:
1. Hold down the INSPECTION button for at least 4 seconds during normal mode to enter the
field setting mode.
2. Press the MODE button to select the desired mode No.
3. Press the FAN or BACK LIGHT button to select the first code No.
4. Press the TEMP button to select the second code No.
5. Press the RESERVE button to set the present settings.
6. Press the INSPECTION button to return to the normal mode.
Mode No.
5
2
1,6
4
3
First code
No.
Second
code No.