SiAF332111E Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation 105
1.4.21 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment
(11 (21)-7), or manually using external static pressure settings (13 (23)-6).
FXMQ-PB
: Factory setting
1 FXMQ40PB cannot be set to 180 or 200 Pa.
2 FXMQ50-125PB cannot be set to 30 Pa.
3 FXMQ140PB cannot be set to 30 Pa and 150-200 Pa.
1.4.22 Setting of Swing Patterns when Cooling Thermostat is OFF
In cooling operation, when the airflow direction is set to swing, flaps swing even when the
thermostat is OFF. This setting allows to change the airflow direction when the thermostat is
OFF.
: Factory setting
1.4.23 Setting of Circulation Airflow
This is to set whether the circulation airflow function is enabled or disabled.
: Factory setting
Mode No. First Code No. Second Code No. Contents
13 (23) 6
01 30 Pa (2) (3)
02 50 Pa
03 60 Pa
04 70 Pa
05 80 Pa
06 90 Pa
07
100 Pa
08 110 Pa
09 120 Pa
10 130 Pa
11 140 Pa
12 150 Pa (3)
13 160 Pa (3)
14 180 Pa (1) (3)
15 200 Pa (1) (3)
Mode
No.
First
Code No.
Second
Code No.
Fixed Swing
13 (23) 7
01 Set Position Swing
02 Set Position P0
03
P0 P0
04 Set Position Swing
05 Set Position P2
06 P2 P2
07 Set Position Swing
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23) 13
01 Disabled
02
Enabled