Field Settings for Outdoor Unit (4/5 HP Models) SiAF332111E
116 Part 5 Field Settings and Test Operation
Press the SET (BS2) button and match with the LEDs No. 1 - 15, push the RETURN (BS3)
button, and confirm the data for each setting.
Data such as addresses and number of units is expressed as binary numbers; the two ways
of expressing are as follows:
Refer to the preceding page for a list of data, etc. for No. 0 - 25.
The No. 2 Low noise / demand address is expressed as a binary number
consisting of the lower 6 digits. (0 - 63)
In the figure 1, the address is 010110 (binary number), which translates to
16 + 4 + 2 = 22 (base 10 number). In other words, the address is 22.
The number of terminal blocks for No. 12 and 13 is expressed as an 8-digit
binary number, which is the combination of four upper, and four lower
digits for No. 12 and 13 respectively. (0 - 128)
In the figure 2, the address for No. 12 is 0101, the address for No. 13 is
0110, and the combination of the two is 01010110 (binary number), which
translates to 64 + 16 + 4 + 2 = 86 (base 10 number). In other words, the
number of terminal block is 86.
l hlhllh
16 4 1
32 8 2
Figure 1
lhh hlhl
64 16
128 32
No.12
lhh hllh
4 1
No.13
8
2
Figure 2