Field Settings for Outdoor Unit (6/8 HP Models) SiAF332111E
134 Part 5 Field Settings and Test Operation
Setting does not return to factory setting when exit mode 2. To cancel the function, change
setting manually to factory setting.
Once function is activated t01 appears. To stop current function, press once BS3 “Return”
button.
For detailed description about each setting, refer to Details of Setting Mode (Mode 2) on page
135.
Indication bold means factory setting.
No.
Item Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
29
Capacity priority Cancel the low noise level control if
capacity is required while low noise
operation or night-time low noise
operation is in progress.
2. 2 9
OFF
ON
0
1
30
Demand 1
setting
Used to make a change to the targeted
power consumption level when the
demand 1 control signal is inputted.
2. 3 0
Level 1 (60%)
Level 2 (65%)
Level 3 (70%)
Level 4 (75%)
Level 5 (80%)
Level 6 (85%)
Level 7 (90%)
Level 8 (95%)
1
2
3
4
5
6
7
8
31
Demand 2
setting
Used to use a targeted power current
level when the demand 2 control signal
is inputted.
2. 3 1
Level 1 (40%)
Level 2 (50%)
Level 3 (55%)
1
2
3
32
Constant
demand setting
Used to set constant demand 1 or 2
control without inputting any external
signal.
2. 3 2
OFF
Demand 1 (Mode 2-30)
Demand 2 (Mode 2-31)
0
1
2
34
Indoor fan upper
limit
Forced fan speed to low indoor units
thermostat ON if total indoor
thermostat-ON > index 130.
2. 3 4
Cooling and heating
Heating only
Never
0
1
2
35
Tc target setting To change Tc target cooling.
2. 3 5
Higher
Lower
Do not use
0
1
~7
42
Outdoor fan Outdoor fan noise countermeasure (limit
fan speed). 2. 4 2
Standard
Mode A
Mode B
0
1
2
76
VRTsmart
control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRTsmart
control.
2. 7 6
Low 1
Low 2
Low 3
Low 4
Low 5
Low 6
Standard
High
0
1
2
3
4
5
6
7
78
VRT control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRT control. 2. 7 8
Standard
High
4
6
81
Cooling comfort setting
2. 8 1
ECO
Mild
Quick
Powerful
0
1
2
3
83
Master remote control setting when mix combination
2. 8 3
VRV indoor
RA indoor
——
0
1
90
Indoor unit
without power
Possible for operate system when some
indoor units are temporary without
power supply.
2. 9 0
Disabled
Enabled
0
1
95
Eco level setting for VRTsmart
2. 9 5
Standard
Middle
High
0
1
2
96
Eco level setting for Eco mode by main PCB
2. 9 6
OFF
Low
Standard
0
1
2