Field Settings for Outdoor Unit (10/12 HP Models) SiAF332111E
150 Part 5 Field Settings and Test Operation
In Setting mode and Confirmation mode operate according to
the following sequences.
Settings
Seven-segment display
SEG1 SEG2 SEG3
Setting
sequences
(1) Press the SET button (BS2) to set the
seven-segment display to any of the setting
items ((A) to (G)) listed in the table on the right.
(1) Set outdoor unit low noise operation and
query through the external controller (optional
accessory) for cooling/heating selector operation
settings.
Refer to the optional accessories manual for
details.
(A) For selecting cooling/heating
mode (1)
200
(B) For charging additional refrigerant
for operation
220
(C) For setting refrigerant
recycle/vacuum mode
221
(D) For setting night-time low noise
mode
222
(E) For setting external low noise
level (1)
225
(F) For setting the demand level (1)230
(G) For external low noise demand
(1)
212
(2) Press the RETURN button (BS3). (Displays the current set value) Any of the displays in (3)
(3) Press the SET button (BS2) to set
the seven-segment display to any of
the setting items listed in the table on
the right.
For (A) Cooling/heating mode switching of
individual units in various outdoor unit
systems
OFF OFF 0
For
(B)(C)(G)
ON OFF OFF 1
OFF (Default) OFF OFF 0
For (D)
(2)
OFF (Default) OFF OFF 0
Level 1 OFF OFF 1
Level 2 OFF OFF 2
Level 3 OFF OFF 3
For (E)
(2)
Level 1 OFF OFF 1
Level 2 (Default) OFF OFF 2
Level 3 OFF OFF 3
For (F)
(2)
Level 1 OFF OFF 1
Level 2 OFF OFF 2
Level 3 (Default) OFF OFF 3
Level 4 OFF OFF 4
Level 5 OFF OFF 5
Level 6 OFF OFF 6
Level 7 OFF OFF 7
Level 8 OFF OFF 8
(4) Press the RETURN button (BS3) Verify the set value in (3) The upper display stops
blinking and is turned ON.
(5) Press the RETURN button (BS3)
again
Operate according to the settings
200
(6) Press the MODE button (BS1) Return to normal mode OFF OFF OFF
Confirmation
sequences
(1) Press the SET button (BS2) to set
the seven-segment display to the
setting items ((H)/(J)) listed in the
table on the right.
(H) For low noise operation 1 0 1
(J) For operation demand
102
(2) Press the RETURN button (BS3).
(Displays the current set value)
During setting operation OFF OFF 1
During normal operation OFF OFF 0
1
12345678
23
Level
(2) Effects of level setting
Level
Noise level
(D) (E)
(F)
Low noise
(3) Effects of level setting
Power consumption
Power-saving value